PEMETAAN INTENSITAS POLUSI PADA ISOLATOR JARINGAN TRANSMISI
Keywords:
insulator, pollutan, ESDD, NSDDAbstract
The problem in this study were: (1) how the intensity of pollution sector in the region polluted insulator, (2) how polluted insulator surface conductivity Parent substations in each region, (3) how to profile an appropriate insulators for
substations with different levels of intensity of pollution sector in the region. To solve this problem pollutant sampling
conducted on ceramic insulators on the channel milestone substation switchyard each region at two different points, namely
at the top of the insulator and the bottom fin insulators. The results showed the intensity of pollution for every region of
substation at a concentration of 0.50 g / l has a value of ESDD with dissolved heavy pollutant levels (> 0.1 mg/cm2), while the
value of NSDD categorized insoluble lowlevel pollutants. Maximum leakage current value obtained by GI. Makale 4.73
mA, GI. Sungguminasa 4.47 mA, GI. Tello 4.60 mA, GI. Long Tallo 4.67 mA and GI. Pangkep 4.87 mA.
Downloads
Published
How to Cite
Issue
Section
License
Copyright (c) 2011 Lanto Mohamad Kamil Amali
This work is licensed under a Creative Commons Attribution 4.0 International License.