ANALISIS PENGUJIAN ARUS BOCOR LINE POST INSULATOR 70 kV YANG TERKONTAMINASI POLUTAN INDUSTRI

Authors

  • Lanto Mohamad Kamil Amali

Keywords:

Insulator, Current leakage, Flashover

Abstract

Failure of Insulators of ‘Line Post Insulator 70 kV type’ usually caused by many factors, such as the leakage current on
contaminated insulator surfaces. This leakage current will cause interference with the electrical energy distribution system. This
study reported the results of testing the leakage current on insulator 70 kV Line Post Insulator type performed on high-voltage
laboratory Ujung Pandang State Polytecchnics. Based on testing, the maximum leakage current value obtained in wet conditions polluted with spraying of pollutants ESDD = 3.2 mg/cm2 and NSDD = 0.08 mg/cm2 with a value of leakage current
of 7.4 mA at an applied voltage of 22 kV, this can result in flashover.

Downloads

Published

2011-09-01

How to Cite

[1]
L. M. Kamil Amali, “ANALISIS PENGUJIAN ARUS BOCOR LINE POST INSULATOR 70 kV YANG TERKONTAMINASI POLUTAN INDUSTRI”, Fs, vol. 2, no. 1, Sep. 2011.